VAV Box Calculator

Size VAV terminal boxes with min/max CFM, reheat capacity, and inlet sizing.

Zone Parameters

Maximum Cooling CFM
--
CFM (design airflow)
Minimum CFM
--
Inlet Size
--
inches (round)
Reheat Capacity
--
BTU/hr
Discharge Air Temp (heat)
--
°F
Inlet Velocity
--
ft/min
Ventilation Min CFM
--
CFM (ASHRAE 62.1)
Recommended VAV Box
--

VAV Box Sizing

Max CFM = Cooling Load / (1.08 x (Room Temp - Supply Air Temp))

Min CFM = Max CFM x Min Flow %

Reheat = 1.08 x Min CFM x (Discharge Temp - Supply Temp)

  • Cooling only VAV: Throttles airflow from max to min based on zone demand
  • Reheat VAV: Adds heating coil for zones that need heating at minimum flow
  • Fan-powered: Has a small fan to maintain minimum flow even when primary air reduces
  • Minimum flow typically 30-50% for reheat, 20-30% for cooling only