VAV Box Sizing
Max CFM = Cooling Load / (1.08 x (Room Temp - Supply Air Temp))
Min CFM = Max CFM x Min Flow %
Reheat = 1.08 x Min CFM x (Discharge Temp - Supply Temp)
- Cooling only VAV: Throttles airflow from max to min based on zone demand
- Reheat VAV: Adds heating coil for zones that need heating at minimum flow
- Fan-powered: Has a small fan to maintain minimum flow even when primary air reduces
- Minimum flow typically 30-50% for reheat, 20-30% for cooling only